Siemens SENTRON 3VM1112-5GE42-0AA0 – Thermal Magnetic Trip Unit MCCB
The Siemens 3VM1112-5GE42-0AA0 is a SENTRON 3VM molded case circuit breaker (MCCB) designed for reliable protection of low-voltage electrical distribution systems against overload and short-circuit faults. It is widely used in industrial switchboards, MCC panels, and power distribution networks where dependable feeder protection and stable performance are required.
This model belongs to the 3VM1 IEC Frame 160 series and is equipped with a TM220 thermal magnetic trip unit (ATFM – Adjustable Thermal, Fixed Magnetic). It provides adjustable overload protection and fixed instantaneous short-circuit protection, ensuring both flexibility and safety in industrial applications.
With a rated current of 125 A and a high breaking capacity of up to 55 kA at 415 V AC (variant dependent), it is suitable for demanding industrial feeder and distribution applications.
Key Features:
• Siemens SENTRON 3VM MCCB
• TM220 thermal magnetic trip unit (ATFM)
• 4-pole configuration
• Rated current: 125 A
• Adjustable overload protection (Ir: approx. 88–125 A)
• Fixed instantaneous short-circuit protection (Ii: 10 × In)
• High breaking capacity for industrial distribution use
• IEC Frame 160 compact design
• Front terminal connection system
• Suitable for MCC, PCC, and feeder applications
• Reliable industrial-grade construction
• IEC 60947-2 compliant
Technical
Specifications
|
Parameter |
Specification |
|
Product
Model |
3VM1112-5GE42-0AA0 |
|
Brand |
Siemens |
|
Series |
SENTRON
3VM |
|
Type |
Molded
Case Circuit Breaker (MCCB) |
|
Trip
Unit |
TM220
(ATFM) |
|
Number
of Poles |
4
Pole |
|
Rated
Current (In) |
125
A |
|
Overload
Protection (Ir) |
88–125
A (adjustable) |
|
Short-Circuit
Protection (Ii) |
10
× In (fixed) |
|
Frame
Size |
160 |
|
Breaking
Capacity |
Up
to 55 kA at 415 V AC (variant dependent) |
|
Rated
Voltage (Ue) |
Up
to 690 V AC |
|
Rated
Insulation Voltage (Ui) |
800
V |
|
Frequency |
50/60
Hz |
|
Mounting
Type |
Fixed
mounting |
|
Connection
Type |
Front
terminal |
|
Mechanical
Life |
~15,000
operations |
|
Electrical
Life |
~6,000
operations |
|
Standards |
IEC
60947-2 |
No reviews yet.