Siemens SENTRON 3VM MCCB – Thermal Magnetic Trip Unit – 3VM1132-5GE42-0AA0
The Siemens 3VM1132-5GE42-0AA0 is a SENTRON 3VM1 series molded case circuit breaker (MCCB) designed for protection of low-voltage electrical distribution systems against overload and short-circuit faults. It is widely used in industrial switchboards, MCC panels, and feeder distribution systems where high fault-level protection and compact design are required.
This model belongs to the 3VM1 Frame 160 series and is equipped with a thermal magnetic trip unit (TM220 / ATFM – Adjustable Thermal, Fixed Magnetic). It provides adjustable overload protection (Ir: approx. 22–32 A) and fixed instantaneous short-circuit protection (Ii ≈ 10 × In), ensuring reliable coordination with downstream protection devices.
With a rated current of 32 A and a high breaking capacity of 55 kA at 415 V AC, it is suitable for industrial installations with high prospective fault levels, offering strong short-circuit interruption capability and dependable feeder protection.
Key Features:
• Siemens SENTRON 3VM1 MCCB (Frame 160 series)
• Thermal Magnetic (TM220 / ATFM) protection system
• Adjustable overload protection (approx. 22–32 A)
• Fixed instantaneous short-circuit protection
• 4-pole configuration (3P + Neutral support variants in family)
• Rated current: 32 A
• Breaking capacity: 55 kA at 415 V AC
• Suitable for feeder and distribution protection
• IEC 60947-2 compliant
• Compact industrial MCCB design
|
Parameter |
Specification |
|
Product Model |
3VM1132-5GE42-0AA0 |
|
Brand |
Siemens |
|
Series |
SENTRON 3VM1 |
|
Type |
MCCB (Molded Case Circuit Breaker) |
|
Trip Unit |
TM220 (Thermal Magnetic ATFM) |
|
Rated Current |
32 A |
|
Number of Poles |
4 Pole |
|
Breaking Capacity (Icu) |
55 kA @ 415 V AC |
|
Overload Setting Range |
~22–32 A |
|
Instantaneous Protection |
Fixed (≈10 × In) |
|
Frame Size |
3VM1 Frame 160 |
|
Rated Voltage |
Up to 690 V AC |
|
Mounting Type |
Fixed mounting |
|
Standards |
IEC 60947-2 |
No reviews yet.