The Siemens 5SU1344-1RC40 is a SENTRON / Betagard 5SU1 Residual Current Circuit Breaker with Overcurrent Protection (RCBO) designed to combine overload, short-circuit and residual-current protection in one device. The exact Siemens product configuration is 40 A, 4-pole, 8-module, C characteristic, Type AC and 30 mA residual-current sensitivity. The Siemens technical data specifies 415 V AC, 50 Hz, 10 kA short-circuit breaking capacity according to EN 61009-1, and 15 kA switching capacity according to IEC 60947-2. It also carries the important note that use of these devices is not permitted in all countries; national installation regulations must be observed.
The 5SU1344-1RC40 belongs to the Siemens SENTRON / Betagard 5SU1 RCBO family.
An RCBO combines three protection functions in one device:
Overload protection
Short-circuit protection
Residual-current protection
This integrated construction can simplify circuit-level protection compared with using separate MCB and RCCB devices.
The exact product listing confirms 40 A, 4-pole, 8 modules, C characteristic, Type AC and 30 mA.
The 5SU1344-1RC40 has a rated current of 40 A.
It is suitable for compatible three-phase circuits and feeders designed around a 40 A protective device. The final rating should be coordinated with cable ampacity, connected load, installation method, ambient conditions and applicable electrical requirements.
The RCBO uses a C tripping characteristic.
C-curve protection is intended for compatible circuits where moderate starting or inrush current can occur during normal operation.
Potential applications include:
Pumps
Fans
Motors
Control transformers
Contactors
Solenoids
Industrial auxiliary equipment
Selected machinery
The actual tripping characteristic should be matched to the load's starting-current characteristics and protection coordination.
The 5SU1344-1RC40 uses Type AC residual-current protection.
Type AC is intended for compatible sinusoidal AC residual currents. The residual-current waveform of connected equipment should be checked before selecting this type.
Equipment capable of generating pulsating DC or other residual-current components may require a different residual-current protection type.
The Siemens data identifies the exact article as Type AC.
The RCBO has a rated residual operating current of 30 mA.
When the residual-current condition reaches the specified operating threshold, the RCBO disconnects the protected circuit.
The 30 mA sensitivity should be selected according to the complete protection design and applicable national installation regulations.
The device has 4 poles, making it suitable for compatible three-phase-plus-neutral electrical systems.
The four-pole arrangement allows the three phases and neutral to be incorporated into the circuit protection arrangement.
Typical applications include:
Three-phase distribution boards
Industrial feeder circuits
PCC panels
MCC panels
Commercial three-phase panels
Machine power circuits
Factory electrical systems
Sub-distribution boards
The Siemens technical data specifies 4 poles with protection.
The exact technical data specifies a 415 V AC supply voltage and 50 Hz operating frequency.
This makes the device suitable for compatible three-phase low-voltage electrical systems matching its specified ratings.
The 5SU1344-1RC40 has a 10 kA short-circuit breaking capacity according to EN 61009-1.
The same technical data specifies:
10 kA according to EN 60898
15 kA according to IEC 60947-2
10 kA rated residual switching capacity according to IEC 61009-1
Energy limitation class 3
The prospective short-circuit current at the installation point should still be verified during system design.
A conventional circuit may use:
MCB + RCCB
An RCBO combines these functions:
RCBO = Overload + Short Circuit + Residual Current Protection
This can simplify circuit-level protection and reduce the number of separate protection components in an electrical panel.
The supplied product designation specifies 8 modules. The current technical data specifies 7 modular width units and a physical width of 126 mm for the device.
For the SB Smart product page, the supplied official product designation “8 modules” can be retained in the product title, while the physical modular-width information can be shown separately.
The module designation refers to physical panel space and does not represent a power rating.
The Siemens technical data specifies approximately:
Height: 90 mm
Width: 126 mm
Depth: 70 mm
Installation depth: 70 mm
Modular width units: 7
Mounting position: Any
These dimensions are useful for panel builders when checking DIN-rail and enclosure space.
The Siemens 5SU1 RCBO family is designed for modular electrical installation.
The 5SU1344-1RC40 can be integrated into suitable:
Distribution boards
Industrial control panels
PCC panels
MCC panels
Commercial switchboards
Machine panels
Factory electrical enclosures
Installation should follow Siemens' current mounting and wiring instructions.
The technical data specifies neutral conductor switching.
This supports the four-pole arrangement used in compatible three-phase-plus-neutral systems.
The power-supply connection can be positioned either at the top or bottom.
This provides flexibility during electrical-panel wiring.
The overcurrent section protects the connected circuit against sustained excessive current caused by overload.
The 40 A rating should be coordinated with:
Cable ampacity
Connected load
Installation method
Ambient temperature
Protection-coordination requirements
The RCBO also provides integrated short-circuit protection.
Its 10 kA EN 61009-1 breaking capacity should be evaluated against the prospective fault current at the installation point.
Residual current occurs when part of the electrical current flows through an unintended path, such as leakage toward earth.
The RCBO monitors this condition and disconnects the protected circuit when the specified 30 mA threshold is reached.
This adds residual-current protection to the integrated overload and short-circuit functions.
The C characteristic can be suitable for compatible loads with moderate starting or inrush current.
Potential applications include:
Pumps
Fans
Motors
Solenoids
Contactors
Control transformers
Industrial machinery
Automation equipment
The actual suitability depends on the connected load and protection coordination.
Type AC protection can be suitable for compatible circuits carrying sinusoidal AC residual currents.
For equipment containing rectifiers, variable-speed drives or other power electronics, the required residual-current type should be verified before selecting Type AC.
The 5SU1344-1RC40 can be considered for compatible:
Industrial distribution boards
Three-phase equipment feeders
PCC panels
MCC panels
Machine power circuits
Commercial switchboards
Factory electrical systems
Sub-distribution boards
Building electrical panels
A typical arrangement can be:
Incoming Supply → RCBO → Protected Three-Phase Load
The complete protection design should consider:
Prospective short-circuit current
Cable capacity
Load current
C-curve characteristics
30 mA residual-current sensitivity
Upstream protection
Applicable electrical standards
RCBOs should be included in an appropriate electrical inspection and testing program.
The device's test function should be operated according to Siemens' instructions and applicable maintenance requirements to verify residual-current operation.
Before selecting the 5SU1344-1RC40, verify:
Rated current: 40 A
Residual-current sensitivity: 30 mA
Residual-current type: Type AC
Tripping characteristic: C
Pole configuration: 4-pole
Rated voltage: 415 V AC
Operating frequency: 50 Hz
Short-circuit breaking capacity: 10 kA according to EN 61009-1
Panel space requirements
Cable size and installation method
Load inrush characteristics
Applicable national installation regulations
The exact Siemens product description explicitly states:
“Use of these devices is not permitted in all countries. Observe national installation regulations!”
This warning should be retained on the SB Smart product page because the permitted use of this RCBO depends on the electrical installation rules applicable in the country of installation.
For India, the installer should verify the applicable Indian requirements and Siemens' current product documentation before installation.
The 5SU1344-7RC40 is the corresponding 40 A, 4-pole, 7-module, C-characteristic, Type A, 30 mA configuration.
Therefore:
5SU1344-1RC40 → Type AC, 40 A, 30 mA
5SU1344-7RC40 → Type A, 40 A, 30 mA
The main differences are the residual-current type and modular configuration.
The 5SU1344-2RC40 is the corresponding 40 A, 4-pole, 8-module, D-characteristic, Type AC, 30 mA configuration.
Therefore:
5SU1344-1RC40 → C characteristic
5SU1344-2RC40 → D characteristic
The principal difference is the overcurrent tripping characteristic.
A Type AC C-characteristic 40 A RCBO with 100 mA residual-current sensitivity belongs to a different 5SU1 configuration.
Therefore:
5SU1344-1RC40 → 40 A, Type AC, 30 mA
The residual-current sensitivity should always be checked before selecting an alternative.
The 5SU1644-1RC40 is the corresponding 40 A, 4-pole, C-characteristic, Type AC, 300 mA configuration.
Therefore:
5SU1344-1RC40 → 40 A, Type AC, 30 mA
5SU1644-1RC40 → 40 A, Type AC, 300 mA
The principal difference is the residual-current operating threshold.
The corresponding 32 A Type AC C-characteristic 30 mA version belongs to the same product family.
Therefore:
5SU1344-1RC32 → 32 A
5SU1344-1RC40 → 40 A
The main difference is rated current.
The corresponding 63 A Type AC C-characteristic 30 mA version is used where the protected circuit requires a higher rated current.
Therefore:
5SU1344-1RC40 → 40 A
5SU1344-1RC63 → 63 A
The correct current rating must match the protected circuit and conductor capacity.
The Siemens 5SU1354 and 5SU1624 ranges include 2-pole RCBOs for compatible single-phase applications.
The 5SU1344-1RC40 is a 4-pole device intended for compatible three-phase-plus-neutral circuits.
The pole configuration should therefore be checked carefully before selecting a replacement.
The 5SU1344-1RC40 is an RCBO.
An RCCB primarily provides residual-current protection and normally requires separate overcurrent protection.
An RCBO combines:
Residual-current protection + overload protection + short-circuit protection
in one device.
The Siemens 5SU1344-1RC40 is relevant for:
Electrical panel builders
Industrial buyers
Electrical contractors
OEMs
Machine builders
Factory maintenance teams
Commercial electrical contractors
Electrical distributors
Automation system integrators
Electrical product dealers
For SB Smart, the product is positioned as a Siemens SENTRON / Betagard 5SU1 Type AC RCBO for 40 A three-phase circuit protection with C characteristic and 30 mA sensitivity.
| Specification | Details |
|---|---|
| Brand | Siemens |
| Product Family | SENTRON / Betagard 5SU1 |
| Article Number | 5SU1344-1RC40 |
| Product Type | Residual Current Circuit Breaker with Overcurrent Protection (RCBO) |
| Rated Current | 40 A |
| Number of Poles | 4 Pole / 4P |
| Number of Protected Poles | 4 |
| Tripping Characteristic | C Curve |
| Residual Current Type | Type AC |
| Rated Residual Operating Current | 30 mA |
| Rated Operating Voltage | 415 V AC |
| Operating Frequency | 50 Hz |
| Insulation Voltage (Ui) | 440 V |
| Surge Voltage Resistance | 4 V as stated in the supplied technical data |
| Short-Circuit Breaking Capacity | 10 kA according to EN 61009-1 |
| EN 60898 Switching Capacity | 10 kA |
| IEC 60947-2 Switching Capacity | 15 kA |
| Rated Residual Switching Capacity | 10 kA |
| Energy Limitation Class | 3 |
| Overvoltage Category | III |
| Pollution Degree | 2 |
| Protection Degree | IP20 when installed in a suitable distribution board |
| Neutral Conductor Switching | Yes |
| Touch Protection | Yes |
| Power Supply Position | Top or bottom |
| Height | 90 mm |
| Width | 126 mm |
| Depth | 70 mm |
| Installation Depth | 70 mm |
| Technical Modular Width | 7 units |
| Market Product Designation | 8 modules |
| Mounting Position | Any |
| Ambient Operating Temperature | -5 °C to +45 °C |
| Maximum Relative Humidity | 95% |
| Country Restriction Note | Use not permitted in all countries; observe national installation regulations |
These specifications are taken from the current technical data for 5SU1344-1RC40.
Siemens SENTRON / Betagard 5SU1 RCBO
Article number 5SU1344-1RC40
40 A rated current
4-pole configuration
8-module product designation
Type AC residual-current protection
30 mA residual-current sensitivity
C tripping characteristic
415 V AC rated voltage
50 Hz operating frequency
10 kA EN 61009-1 short-circuit breaking capacity
15 kA IEC 60947-2 switching capacity
10 kA rated residual switching capacity
Neutral conductor switching
Touch protection
Top or bottom power-supply connection
Integrated overload and short-circuit protection
Integrated residual-current protection
Suitable for compatible three-phase-plus-neutral circuits
National installation regulations must be observed
Combined protection: Integrates overload, short-circuit and residual-current protection.
40 A rating: Suitable for compatible three-phase circuits and feeders.
Type AC protection: Designed for compatible sinusoidal AC residual currents.
30 mA sensitivity: Provides residual-current protection at the specified threshold.
C characteristic: Suitable for compatible loads with moderate inrush current.
4-pole design: Suitable for compatible three-phase-plus-neutral systems.
Compact modular construction: Suitable for distribution boards and electrical panels.
10 kA breaking capacity: Provides substantial short-circuit interruption capability within specified conditions.
Neutral switching: Supports the four-pole circuit arrangement.
Flexible supply connection: Power can be connected from the top or bottom.
The Siemens 5SU1344-1RC40 combines 40 A overcurrent protection, C-curve tripping and Type AC 30 mA residual-current protection in a 4-pole RCBO.
The exact Siemens data confirms 415 V AC, 50 Hz, 40 A, 4-pole configuration, Type AC, 30 mA sensitivity, C characteristic and 10 kA EN 61009-1 short-circuit breaking capacity.
For SB Smart, this product is best presented as a Siemens Betagard/SENTRON 5SU1 Type AC RCBO for 40 A, 30 mA three-phase circuit protection with C characteristic across India.
The country-use warning should remain visible on the product page because Siemens explicitly states that use is not permitted in all countries and national installation regulations must be observed.
SB Smart supplies Siemens SENTRON/Betagard RCBOs, RCCBs and industrial electrical protection products across Faridabad, Gurgaon/Gurugram, Delhi NCR, Haryana, Noida, Punjab, Mumbai and other major Indian cities.
The 5SU1344-1RC40 is a Siemens SENTRON / Betagard 5SU1 RCBO rated at 40 A, with 4 poles, C characteristic, Type AC residual-current protection and 30 mA sensitivity.
It is an RCBO, meaning it combines residual-current and overcurrent protection.
The rated current is 40 A.
The rated residual operating current is 30 mA.
It uses Type AC residual-current protection.
It has a C tripping characteristic.
It has 4 poles, suitable for compatible three-phase-plus-neutral applications.
The product designation specifies 8 modules, while the technical data lists 7 modular width units and a physical width of 126 mm.
The exact Siemens data specifies 415 V AC at 50 Hz.
The specified short-circuit breaking capacity is 10 kA according to EN 61009-1.
No. Siemens explicitly states that use of these devices is not permitted in all countries and that national installation regulations must be observed.
5SU1344-1RC40: 40 A, 4-pole, Type AC, 30 mA, C characteristic.
5SU1344-2RC40: 40 A, 4-pole, Type AC, 30 mA, D characteristic.
The main difference is the overcurrent tripping characteristic.
5SU1344-1RC40: Type AC, 40 A, 30 mA, C characteristic.
5SU1344-7RC40: Type A, 40 A, 30 mA, C characteristic.
The main difference is the residual-current type.
5SU1344-1RC40: 40 A, Type AC, 30 mA.
5SU1644-1RC40: 40 A, Type AC, 300 mA.
The principal difference is the residual-current sensitivity.
SB Smart supplies Siemens SENTRON/Betagard 5SU1 RCBOs and industrial electrical protection products in India for panel builders, electrical contractors, OEMs, industrial buyers, machine builders and maintenance requirements.
|
Parameter |
Specification |
|
Product Series |
Siemens Betagard 5SU1 |
|
Part Number |
5SU1344-1RC40 |
|
Product Type |
RCBO |
|
Poles |
4P |
|
Rated Current |
40A |
|
Tripping Curve |
C Curve |
|
Residual Current |
30 mA |
|
Residual Type |
AC |
|
Rated Voltage |
415V AC |
|
Breaking Capacity |
10 kA |
|
Mounting Type |
DIN Rail |
|
Function |
Overload + Short circuit + Earth leakage protection |