The Siemens 5SV4344-0RC is a SENTRON 5SV4 residual current operated circuit breaker (RCCB) designed for residual-current protection in suitable three-phase AC electrical installations with neutral. It is a 4-pole / 3+N, Type AC RCCB with a 40 A rated current and 30 mA rated residual operating current. Siemens' technical data identifies the corresponding 5SV4344-0 as an instantaneous 4-pole Type AC RCCB, rated 40 A, 30 mA and 400 V AC.
The India-facing product designation specifies 415 V, 4MW, making it suitable for compatible three-phase distribution boards, electrical panels and feeder applications.
The 5SV4344-0RC belongs to the Siemens SENTRON 5SV4 RCCB family. Its primary purpose is to detect residual current in the protected circuit and disconnect the circuit when the residual current reaches the specified operating threshold.
Its 4-pole / 3+N configuration is intended for three-phase systems with neutral, making it suitable for industrial, commercial and building electrical distribution applications.
The RCCB has a rated current of 40 A.
This makes it suitable for compatible three-phase circuits and feeders where a 40 A residual-current protection device is required.
The complete electrical installation should ensure that the device operates within its specified current, voltage and environmental conditions.
The 5SV4344-0RC has a rated residual operating current of 30 mA. Siemens specifies the tripping fault current as 30 mA for the corresponding 5SV4344-0 article.
When residual current reaches the specified operating threshold, the RCCB trips and disconnects the protected circuit.
The appropriate residual-current sensitivity should always be selected according to the actual protection design and applicable electrical regulations.
The device is a Type AC RCCB.
Type AC RCCBs are intended for compatible sinusoidal alternating residual currents. The RCCB type should be selected according to the residual-current waveform that may occur in the actual electrical installation.
The 5SV4344-0RC has 4 poles, making it suitable for three-phase plus neutral circuits.
This arrangement allows the three phases and neutral to be incorporated into the residual-current protection scheme.
Typical applications include:
Three-phase distribution boards
PCC panels
MCC panels
Industrial feeders
Commercial electrical panels
Sub-distribution boards
Machine supply circuits
Factory electrical systems
The supplied India product description identifies this model as 415 V AC. Siemens' technical data for the corresponding 5SV4344-0 specifies 400 V AC rated supply voltage.
For the SB Smart product listing, the 415 V India designation can be retained, while actual installation selection should be based on the Siemens-rated system voltage and the electrical installation requirements.
The 5SV4344-0RC is an instantaneous RCCB. Siemens specifies that the switching function is not short-time delayed.
This means the RCCB operates without an intentional short-time delay when the specified residual-current threshold is reached.
Siemens specifies a 10 kA short-circuit current rating for the corresponding 5SV4344-0 article.
The RCCB should nevertheless be coordinated with suitable upstream overcurrent protection and the prospective short-circuit conditions of the installation.
An RCCB primarily provides residual-current protection and should not be treated as a substitute for an MCB or MCCB for overload and short-circuit protection unless the complete protection arrangement specifically provides those functions.
The India product description specifies 4MW, meaning 4 module width.
The 4MW designation refers to the physical modular width of the device and does not mean a 4 MW power rating.
The Siemens 2025 catalogue identifies the Type AC 3P+N 5SV4 family as a 4 MW modular arrangement.
This makes the device suitable for:
Modular distribution boards
Electrical control panels
PCC panels
Sub-distribution boards
Commercial switchboards
Industrial protection assemblies
The 5SV4344-0RC is designed for modular electrical installation.
Siemens identifies the corresponding device as size 1 according to DIN 43880, supporting conventional modular distribution-board arrangements.
The device can be installed alongside compatible MCBs, busbars and other protective accessories according to the panel design.
Siemens specifies 60 mm grid spacing for the corresponding 5SV4344-0 device.
This supports integration into standard modular electrical distribution assemblies.
Residual current occurs when part of the electrical current flows outside the intended circuit path, such as through an unintended earth-leakage path.
The RCCB monitors the relevant current balance and disconnects the protected circuit when the residual current reaches the 30 mA operating threshold.
This provides an additional residual-current protection layer within the overall electrical safety system.
The 5SV4344-0RC can be considered for compatible:
Industrial distribution boards
Commercial electrical panels
Three-phase feeder circuits
PCC and MCC panels
Factory electrical systems
Building distribution systems
Machine supply circuits
Sub-distribution boards
The device is particularly relevant where the protection design requires:
40 A + 30 mA + Type AC + 4-pole / 3+N
This combination can be used for selected three-phase residual-current protection applications.
The use of a 30 mA device should be evaluated against the connected load, leakage-current characteristics and applicable installation requirements.
RCCBs should be included in the electrical installation's regular inspection and testing program.
The test function should be operated according to the manufacturer's instructions and applicable electrical-maintenance requirements to verify correct residual-current tripping.
Regular testing helps confirm that the protective mechanism remains functional.
Before selecting the 5SV4344-0RC, verify:
Rated current: 40 A
Residual-current sensitivity: 30 mA
RCCB type: Type AC
Pole configuration: 4-pole / 3+N
System voltage compatibility
Upstream overcurrent protection
Available panel space: 4 module width
Conductor size and termination
Applicable national electrical regulations
Siemens states that these devices are not permitted in all countries and that national installation regulations must be observed.
The 5SV4342-0 is the corresponding 25 A, 4-pole, Type AC, 30 mA variant, while the 5SV4344-0 is rated at 40 A. Siemens' 2025 catalogue lists both within the same Type AC 3P+N family.
Therefore:
5SV4342-0RC → 25 A, 30 mA
5SV4344-0RC → 40 A, 30 mA
The principal difference is the rated current.
The 5SV4346-0RC is the corresponding 63 A, 4-pole, Type AC, 30 mA version.
Therefore:
5SV4344-0RC → 40 A
5SV4346-0RC → 63 A
The correct rated current should be selected according to the protected circuit.
The 5SV4347-0RC is the corresponding 80 A, 4-pole, Type AC, 30 mA version.
Therefore:
5SV4344-0RC → 40 A
5SV4346-0RC → 63 A
5SV4347-0RC → 80 A
These models share the same Type AC, 4-pole, 30 mA configuration but have different current ratings.
The 5SV4444-0RC is the corresponding 40 A, 4-pole, Type AC, 100 mA version.
Therefore:
5SV4344-0RC → 40 A, 30 mA
5SV4444-0RC → 40 A, 100 mA
The key difference is the residual-current operating threshold.
The 5SV4644-0RC is the corresponding 40 A, 4-pole, Type AC, 300 mA version.
Therefore:
5SV4344-0RC → 40 A, 30 mA
5SV4444-0RC → 40 A, 100 mA
5SV4644-0RC → 40 A, 300 mA
The correct sensitivity should be selected according to the electrical protection scheme.
The 5SV4314-0RC and 5SV4414-0RC are 2-pole / 1+N versions intended for single-phase applications, whereas the 5SV4344-0RC is a 4-pole / 3+N device for three-phase-plus-neutral systems.
Therefore:
5SV4344-0RC → 40 A, 4-pole / 3+N, 30 mA
5SV4314/4414 family → 40 A, 2-pole / 1+N variants
The Siemens 5SV4344-0RC is relevant for:
Electrical panel builders
Industrial buyers
Electrical contractors
Commercial electrical contractors
Facility-maintenance teams
Machine builders
OEMs
Electrical distributors
Factory maintenance departments
Electrical product dealers
For SB Smart, the product is positioned as a Siemens SENTRON/Betagard 5SV4 Type AC RCCB for 40 A three-phase residual-current protection.
Siemens SENTRON 5SV4 RCCB
Article number 5SV4344-0RC
40 A rated current
4-pole / 3+N configuration
30 mA residual-current sensitivity
Type AC
Instantaneous operation
400 V AC rated voltage for the corresponding Siemens article
415 V India market designation
4-module installation format
10 kA short-circuit current rating
2,000 V rated insulation voltage
60 mm grid spacing
Suitable for three-phase plus neutral systems
Suitable for modular distribution boards
40 A rating: Suitable for compatible medium-current three-phase circuits.
30 mA sensitivity: Provides residual-current protection at the specified operating threshold.
4-pole / 3+N design: Suitable for three-phase plus neutral systems.
Type AC: Designed for compatible sinusoidal AC residual currents.
Instantaneous operation: Provides rapid residual-current disconnection without intentional short-time delay.
4-module format: Supports standard modular distribution-board installation.
10 kA short-circuit rating: Supports coordination with suitable upstream protective equipment.
SENTRON 5SV4 design: Provides a standardized Siemens residual-current protection solution.
Industrial suitability: Suitable for selected distribution, feeder and electrical-panel applications.
The Siemens 5SV4344-0RC is a 40 A, 4-pole / 3+N, Type AC RCCB with 30 mA residual-current sensitivity, designed for suitable three-phase AC electrical installations. Siemens' technical data identifies the corresponding 5SV4344-0 as an instantaneous 4-pole Type AC RCCB, 40 A, 30 mA, 400 V AC, with a 10 kA short-circuit current rating.
It is suitable for customers looking to buy or source Siemens SENTRON/Betagard 5SV4 RCCBs for industrial distribution boards, commercial electrical panels, three-phase feeders and residual-current protection applications in India.
For SB Smart, this product is best presented as a Siemens 5SV4 residual-current circuit breaker for 40 A three-phase electrical protection across India.
SB Smart supplies Siemens SENTRON/Betagard RCCBs and industrial electrical protection products across Faridabad, Gurgaon/Gurugram, Delhi NCR, Haryana, Noida, Punjab, Mumbai and other major Indian cities.
Major delivery locations include:
Faridabad
Delhi
Gurgaon/Gurugram
Delhi NCR
Noida
Greater Noida
Haryana
Punjab
Mumbai
Pune
Ahmedabad
Bengaluru
Hyderabad
Chennai
Kolkata
Jaipur
Chandigarh
Lucknow
Indore
Surat
Vadodara
Nagpur
Coimbatore
And other major cities across India
The 5SV4344-0RC is a Siemens SENTRON 5SV4 residual-current operated circuit breaker rated at 40 A, with 4 poles / 3+N, 30 mA residual-current sensitivity and Type AC characteristics.
It has 4 poles, suitable for three-phase plus neutral applications.
The rated current is 40 A.
The rated residual operating current is 30 mA.
It is a Type AC residual-current circuit breaker intended for compatible AC residual currents.
Yes. Siemens identifies the corresponding 5SV4344-0 as instantaneous, with no short-time delayed switching function.
Siemens' current technical data specifies 400 V AC for the corresponding 5SV4344-0 article, while the India product description uses 415 V.
4MW means 4 module width in the modular installation format. It does not mean a 4 MW power rating.
The specified short-circuit current rating is 10 kA.
5SV4344-0RC: 40 A, 4-pole, Type AC, 30 mA
5SV4444-0RC: 40 A, 4-pole, Type AC, 100 mA
5SV4344-0RC: 40 A, 30 mA
5SV4644-0RC: 40 A, 300 mA
Both are 4-pole Type AC RCCBs.
SB Smart supplies Siemens SENTRON/Betagard 5SV4 RCCBs and industrial electrical protection products in India for panel builders, electrical contractors, industrial buyers, maintenance teams and distribution applications.
| Parameter | Specification |
|---|---|
| Product Series | Siemens SENTRON 5SV |
| Part Number | 5SV4344-0RC |
| Product Type | RCCB (Residual Current Circuit Breaker) |
| Number of Poles | 4 Pole (3P + N) |
| Rated Current (In) | 40A |
| Residual Current Sensitivity (IΔn) | 30mA |
| Type | AC Type |
| Rated Voltage | 230/400V AC |
| Frequency | 50/60 Hz |
| Mounting Type | DIN Rail |
| Protection Function | Earth Leakage / Shock Protection |
| Standard | IEC 61008-1 / IEC 61009 |
No reviews yet.